SIP-1, SIP-2, SIP-1А, SIP-2А Technical Specifications 16.К17.268-98
Self-bearing wires with insulated conductors are intended for overhead transmission lines and taps to wires inside residential buildings, household outbuildings for the voltage 0.6/1 kV.
|
|
Section, mm2 |
|
SIP-1
SIP-1А |
1х16,0
+1х25,0 |
3х16,0
+1х25,0 |
3х25,0
+1х35,0 |
3х35,0
+1х50,0 |
3х50,0
+1х50,0 |
3х50,0
+1х70,0 |
- |
- |
|
3х70,0
+1х70,0 |
3х70,0
+1х95,0 |
3х95,0
+1х70,0 |
3х95,0
+1х95,0 |
4х16,0
+1х25,0 |
4х25,0
+1х35,0 |
- |
- |
|
SIP-2 |
1х16,0
+1х25,0 |
1х25,0
+1х35,0 |
1х35,0
+1х35,0 |
3х16,0
+1х25,0 |
3х25,0
+1х35,0 |
3х35,0
+1х35,0 |
3х35,0
+1х50,0 |
3х35,0
+1х50,0 |
|
3х50,0
+1х50,0 |
3х70,0
+1х70,0 |
3х70,0
+1х95,0 |
3х95,0
+1х70,0 |
3х95,0
+1х95,0 |
4х16,0
+1х25,0 |
4х25,0
+1х35,0 |
3х25,0
+1х35,0
+1х25,0 |
|
3х35,0+1х35,0+1х25,0 |
3х50,0+1х50,0+1х25,0 |
3х70,0+1х70,0+1х25,0 |
- |
|
SIP-2А |
1х16,0
+1х25,0 |
2х16,0 |
2х25,0 |
3х16,0
+1х25,0 |
3х25,0
+1х35,0 |
3х35,0
+1х50,0 |
3х50,0
+1х50,0 |
- |
|
3х50,0
+1х70,0 |
3х70,0
+1х70,0 |
3х70,0
+1х95,0 |
3х95,0
+1х70,0 |
3х95,0
+1х95,0 |
4х16,0
+1х25,0 |
4х25,0
+1х35,0 |
- |
Structure
- A conductor is made of aluminium and has a circular shape, solid conductors have a section of 16 mm, stranded conductors have other sections, the number of wires in a phase conductor and their electrical resistance are shown in the table below:
|
Nominal Section
of a Phase Conductor,
мм2 |
Number of wires in a conductor,
pieces |
Electrical Resistance
of a Phase Conductor of 1 km Long to a Direct Current
of No More Than, Ohm |
|
16,0 |
1 |
1,910 |
|
25,0 |
7 |
1,200 |
|
35,0 |
7 |
0,868 |
|
50,0 |
7 |
0,641 |
|
70,0 |
7 |
0,443 |
|
95,0 |
7 |
0,320 |
- A bearing zero conductor is uninsulated for SIP-1 and SIP-2, insulated for SIP-1А and SIP-2А, made of aluminium alloy, has a circular shape, is compacted, reinforced with a steel wire:
|
Nominal Section
of a Zero Bearing Conductor,
mm2 |
Number of Wires in a Conductor, Pieces |
Electrical Resistance
of a Zero Bearing Conductor of 1 km Long to a Direct Current
of No More Than, Ohm |
|
Aluminium |
Steel |
|
25,0 |
6 |
1 |
1,380 |
|
35,0 |
6 |
1 |
0,986 |
|
50,0 |
6 |
1 |
0,720 |
|
70,0 |
6 |
1 |
0,493 |
|
95,0 |
6 |
1 |
0,363 |
- The insulation of SIP-1 and SIP-1А is made of light-stabilized thermoplastic polyethylene, the insulation of SIP-2 and SIP-2А is made of light-stabilized cross-linked polyethylene.
Technical characteristics
- The climatic performance of wires is NF, categories of arrangement 1, 2, 3 in accordance with GOST 15150-69. - Wires are resistant to the action of the solar radiation, which can be characterized by the integrated heat flux density of 1120 W/m2±10%, including density of ultraviolet spectrum. - Wires are resistant to bending at a temperature of -40°С - Wire installation and wiring work must be carried out at an ambient temperature of not below -20°С - Allowable effort in a zero conductor at tension and at exploitation is no more than 45 N/mm2 - Insulated wire conductors stand a test by the alternating voltage of 3.5 kV, frequency of 50 Hz for transmission - Wires, after being exposed in water at a temperature of 20±10°С for not less than 10 minutes, stand a test of the alternating voltage with frequency of 50 Hz during 5 mines, which is: 2.5 kV for wires of the marks SIP-1 and SIP-1А 4.0 kV for wires of the marks SIP-2 and SIP-2А - Wires stand a test of the alternating voltage of 4.0 kV, frequency of 50 Hz, within 1 hour - The permissible heating temperature of conductors at exploitation must not exceed the following values: for SIP-1 and SIP-1А: 70°С at a normal mode 80°С at overload conditions of 8 hours per day or less 135°С at a short circuit with short circuit current flow during 5 sec for SIP-2 and SIP-2А: 90°С at a normal mode 130°С at overload conditions of 8 hours per day or less 250°С at a short circuit with short circuit current flow during 5 sec - A factory wire length must be agreed while ordering - A guaranty service life is 3 years from the date of putting cables into operation - A lifetime of wires is 25 years |

|